Torque lb/Nm | 5750 in lbs / 650 Nm | ||||||
---|---|---|---|---|---|---|---|
Supply Voltage | 12 VAC or DC | 24 VAC or DC | 120 VAC | 230 VAC | 230 VAC 3 Phase | 380 VAC 3 Phase | 480 VAC 3 Phase |
Max Inrush Current | 12.5A | 8.5A | 3.8A | 2.0A | 1.8A | 1.3A | 1.4A |
Running Current | 1.3A | 7.0A | 2.1A | 1.1A | 1.0A | 0.7A | 0.6A |
Motor | DC Brush Type | Split Phase Capacitor | Polyphase | ||||
Runtime (90°@60Hz) |
28 sec | 28 sec | 28 sec | ||||
Runtime (90°@50Hz) |
28 sec | 31 sec | 31 sec | ||||
Control | On/Off/Jog/Proportional | On/Off/Jog/Proportional (with or without MCC) | |||||
Weight | 47 lbs/22 kg | 59 lbs/27 kg (w MCC) | |||||
Mechanical Connections | ISO5211 F10 8 pt 35 mm | ||||||
Electrical Entry | (2) 3/4” NPT | ||||||
Electrical Terminations | 12 - 16 Ga. | ||||||
Environmental Rating | NEMA 4/4X | ||||||
Manual Override | 7.6” HandWheel | ||||||
Case Material | Aluminum Alloy, Powder Coated | ||||||
Thermal Limit | 230°F/110°C Thermal F* Class *Totally Enclosed Non-Ventilated Motors |
||||||
Ambient Temperature Operating Range |
-22°F to +125°F -30°C to +52°C |
P6 DC: An electric actuator designed for load requirements ranging up to 5750 in lbs. The actuator comes standard with two auxiliary switches (Form C), an internal
low power heater, a NEMA 4X environmental rating, and in 12 VDC or 24 VDC, supply voltages. The P6 mechanical connections utilize an ISO5211 mounting
system. The P6 Series can be ordered as an on/off or two position model that can also be used in bump/jog applications. Additionally, a proportional
control is available to accept 0-5 VDC, 0-10 VDC, 1-5 VDC or 4-20 mA input signals.
P6 HV: An electric actuator designed for load requirements ranging up to 5750 in lbs. The actuator comes standard with two auxiliary switches (Form C), an
internal low power heater, a NEMA 4X environmental rating, and in 120 VAC or 230 VAC supply voltages. The P6 mechanical connections utilize an
ISO5211 mounting system. The P6 Series can be ordered as an on/off or two position model that can also be used in bump/jog applications. Or it can
be ordered with an advanced internal proportional control card that accepts a wide range of control signals, generates multiple feedback signals, and
has look-ahead fault prevention.
P6 LV: An electric actuator designed for load requirements ranging up to 5750 in lbs. The actuator comes standard with two auxiliary switches (Form C), an internal
low power heater, a NEMA 4X environmental rating, and in 12 VAC, 24 VAC supply voltages. The P6 mechanical connections utilize an ISO5211 mounting
system. The P6 Series can be ordered as an on/off or two position model that can also be used in bump/jog applications. Or it can be ordered with an
advanced internal proportional control card that accepts a wide range of control signals, generates multiple feedback signals, and has look-ahead fault
prevention.
*12 VAC models are not available in proportional control.